15. Choose a pre-defined calculation method based on a tank shape that

corresponds to the actual tank. Choose None if volume calculation is not
desired.
Use Volume Offset if you do not want zero volume and zero level to match
(for example if you want to include the product volume below the zero
level).
The Strapping Table option is used if the actual tank does not match any
of the available options for pre-defined tanks or if a higher calculation
accuracy is desired.

Calculation Method:
F

OUNDATION

Fieldbus parameter:

TRANSDUCER 1300>VOL_VOLUME_CALC_METHOD

Diameter:
F

OUNDATION

Fieldbus parameter:

TRANSDUCER 1300>VOL_IDEAL_DIAMETER

Tank Length:
F

OUNDATION

Fieldbus parameter:

TRANSDUCER 1300>VOL_IDEAL_LENGTH

Volume Offset:
F

OUNDATION

Fieldbus parameter:

TRANSDUCER 1300>VOL_VOLUME_OFFSET

See “Volume Configuration” on page 5-7 for more information.