Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

5-26

Analog Output (HART)

9. Configure the Analog Output

HART command: [2,1, 6].

Analog Output is not available for F

OUNDATION

Fieldbus.

Typically, the Primary Variable (PV) is configured to be Product Level,
Interface Level, or Volume. Other variables like Product Distance, Interface
Distance, Upper Product Thickness, etc. are available as well.

Specify the analog output range by setting the Lower Range Value (4 mA)
and the Upper Range Value (20 mA) to the desired values.

The Alarm Mode specifies the output state when a measurement error occurs.

See also “Analog Output (HART)” on page 5-9 for information on Analog
Output configuration.

Finish Configuration
Wizard

10. Finish the Configuration Wizard

This is the last window in the Configuration Wizard concluding the basic
configuration. The current configuration can be changed at any time by using
the Setup windows (General, Tank, Output etc., see “Using the Setup
Functions” on page 5-18
).
The Setup windows contain further options not available in the configuration
wizard.
Click the Finish button and continue with the next step in the Guided Setup.