Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 274

Advertising
background image

Reference Manual

00809-0100-4530, Rev BA

July 2009

Rosemount 5300 Series

D-4

REMOTE HOUSING
CONFIGURATION

When using remote housing, the remote connection length should be
configured. If the Remote Housing is ordered with a transmitter, it is
configured in the factory.

In Rosemount Radar Master, select Setup > Tank.

Under the Probe tab, Remote Housing length can be selected. Click the Store
button to save changes.

In the 375 Field Communicator, Remote Housing can be set with HART
command [2, 3, 1, 4, 2].

NOTE!
When disconnecting a remote housing cable from a probe in low
temperatures, -22 °F (-30 °C), Radar Master may not show that the probe is
missing.

Advertising