LEVEL AND DISTANCE
CALIBRATION

Level and distance calibration may be necessary when using a nozzle or pipe
or if there are disturbances in the near zone caused by a physical object.

Non-metallic (e.g. plastic) vessels and installation geometry may introduce an
offset for the zero reference point. This offset may be up to ± 25 mm. The
offset can be compensated for using Distance Calibration.

When calibrating the transmitter, it is important that the product surface is
calm and that the tank is not being filled or emptied.

A complete calibration is performed in two steps:

1. Calibrate the Distance measurement by adjusting the Calibration Offset

parameter.

2. Calibrate the Level measurement by adjusting the Tank Height.

Distance calibration

1. Measure the actual distance between the Upper Reference Point and the

product surface.

2. Adjust the Calibration Distance so that the Distance measured by the

transmitter corresponds to the actual distance.
The Calibration Distance parameter is available via
HART command [2, 3, 2, 4, 1],
or
RRM:

a. Click the Tank icon under Device Config/Setup in the RRM

workspace.

b. In the Tank window, select the Geometry tab.

c. Click the Advanced button.

d. Enter the desired value in the Calibration Distance field and click

the Store button.

Level calibration

1. Measure the actual Product Level.

2. Adjust the Tank Height so the product level measured by the transmitter

corresponds to the actual product level.