Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 269

Advertising
background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

C-21

Rosemount 5300 Series

Figure C-18. Check if Signal
Quality Metrics is supported.

3.

If “Diagnostics Suite” is mentioned in the Device Software

Configuration 2 list, the device supports Signal Quality Metrics.

In 375 Field Communicator, if Signal Quality Metrics is supported, it can
be found with the [3, 2, 2, 1] sequence. Check if “Diagnostics Suite” is
present

Signal Quality Metrics can be enabled/disabled in RRM. Choose Tools,
Advanced,
Signal Quality Metrics tab.

NOTE!
If Signal Quality Metrics is not supported or disabled, the Signal Quality and
Surface / Noise Margin will always be set to 0.

Viewing Signal Quality
Metrics in RRM

To view Signal Quality Metrics in RRM, choose the Tools > Device Display
option and select the Signal Quality Metrics tab.

Figure C-19. View Signal Quality
Metrics Values.

Diagnostics
Suite