This section describes error conditions found in the Resource block. Read
Table 7-13 through Table 7-15 to determine the appropriate corrective action.

Block Errors

Table 7-13 lists conditions reported in the BLOCK_ERR parameter.

Table 7-13. Resource Block
BLOCK_ERR messages

Table 7-14. Resource Block
SUMMARY_STATUS messages

Table 7-15. Resource Block
DETAILED_STATUS with
recommended action messages

Condition Name and Description

Other

Simulate Active: This indicates that the simulation switch is in place.
This is not an indication that the I/O blocks are using simulated data

Device Fault State Set

Device Needs Maintenance Soon

Memory Failure: A memory failure has occurred in FLASH, RAM, or EEPROM memory

Lost Static Data: Static data that is stored in non-volatile memory has been lost

Lost NV Data: Non-volatile data that is stored in non-volatile memory has been lost

Device Needs Maintenance Now

Out of Service: The actual mode is out of service

Condition Name

Uninitialized

No repair needed

Repairable

Call Service Center

Condition Name

Recommended Action

LOI Transducer block error

1. Restart processor
2. Check display connection
3. Call service center

Sensor Transducer block error

1. Restart processor
2. Check Rosemount 5300 cable
3. Call service center

Mfg. Block integrity error

1. Restart processor
2. Call service center

Non-Volatile memory integrity error

1. Restart processor
2.Call service center

ROM integrity error

1. Restart processor
2. Call service center