Recommended mounting for solids -13, Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 43

Advertising
background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

3-13

Rosemount 5300 Series

Recommended Mounting
for Solids

Consider the following guidelines when mounting the transmitter:

Do not mount near inlet pipes in order to avoid product filling on the
probe

Regularly check the probe for defects

It is recommended that the vessel be empty during installation

For concrete vessels, the distance (L) between the probe and the wall
should be at least 20 in. (500 mm)

Stabilize the probe for side forces, by attaching the probe to the tank
bottom.
For solids, use the 0.24 in. (6 mm) probe, because of the higher tensile
strength. The probe should have a sag of



1 in./100 in. (1 cm/m) to

prevent probe damage. See “Anchoring“ on page 3-22 for more
information

Avoid anchoring in solids tanks over 98 ft (30 m) in height since tensile
loads are much stronger for anchored probes, see “Considerations for
Solid Applications“ on page 3-6

Product build-up on the silo walls near the probe may interfere with
measurements. Choose a mounting position where the probe is not in
contact with, or close to, the product build-up