Rosemount 5300 Series

Sim mode 0 active

The simulation mode is active. The given
measurements are simulated.

Turn off the simulation mode.

Advanced Simulation Mode
active

The advanced simulation mode is active.

To turn off the Advanced Simulation
mode, set Holding Register 3600=0 (see
“Viewing Input and Holding Registers” on
page 7-27).

Invalid Lower Volume Value

The given lower volume value is invalid.

Check Lower Volume Status for details.

Invalid Upper Volume Value

The given upper volume value is invalid.

Check Upper Volume Status for details.

Using probe end projection
measurement

The probe end projection is active in the
transmitter software.

No action needed.

Reference echo present

An echo has been detected in the
reference zone.

No action needed.

Sudden level jump detected

This may result from various
measurement problems, such as:
1. Rapid level changes
2. Surface level within transition zone
3. Disturbing echo

Check the tank to find out what causes
problem to track the surface.
1. Set the Rapid Level Changes
parameter, see “Tank Environment” on
page 5-6.
2. In the Transition Zones, the level may
jump to Full Tank/End of Probe, see
“Transition Zones” on page 2-10.
3. See “Disturbance Echo Handling” on
page 7-7.

Nearzone echo present

An echo has been detected in the
nearzone.

No action needed.

Nonlinear gain used

The nonlinear gain is enabled.

No action needed.

Nearzone measurement

The current sweep can be used as a
measurement of the nearzone.

No action needed.

Message

Description

Action