Tri-loop hart to analog converter -45, Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 117

Advertising
background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

5-45

Rosemount 5300 Series

TRI-LOOP HART TO
ANALOG CONVERTER

The Rosemount 333 HART Tri-Loop HART-to-Analog Signal Converter is
capable of converting a digital HART burst signal into three additional
4-20 mA analog signals.

To set the Rosemount 5300 transmitter up for the HART Tri-Loop:

1. Make sure the Rosemount 5300 transmitter is properly configured.

2. Assign transmitter variables Primary Variable, Secondary Variable etc.
HART command [2,1,1].
RRM: Setup>Output/General.

3. Configure variable units: Length, Level Rate, Volume and Temperature.
HART command [2,2,2,5].
RRM: Setup>General/Units.

4. Set the 5300 in Burst mode.
HART command [2,2,4,2].
RRM: Setup>General/Communication.

5. Select Burst option 3=Process variables and current (Process vars/crnt).
HART command [2,2,4,2,2].

6. Install the Tri-Loop. Connect Channel 1 wires, and optionally wires for
Channel 2 and Channel 3.

Variables
Assignment

Variable
Units

Advertising