Rosemount 5300 series – Emerson Process Management ROSEMOUNT 5300 User Manual

Page 267

Advertising
background image

Reference Manual

00809-0100-4530, Rev BA
July 2009

C-19

Rosemount 5300 Series

To calibrate Dynamic Vapor Compensation:

1. Either choose Device Specific Configuration in the Guided Setup (if

the configuration is recommended) or Setup, Advanced.

2. Select the Vapor Compensation tab.

Figure C-16. Calibrate Dynamic
Vapor Compensation.

3. Click the Calibrate Vapor Compensation button.

4. Make sure Use Vapor Compensation is selected.

5. The echo from the reference reflector end can be viewed in the Echo

Curve in RRM. Probes shorter than 6.6 ft. (2 m) will have the reflector
end at 0.75 ft. (0.23 m) distance and probes longer than 6.6 ft. (2 m) will
have the reflector end at 1.6 ft. (0.5 m).

6. Cycle power to finish.

In 375 Field Communicator, the calibration can be done by HART command
[2, 7, 3].