Unit installation – Garland JACK IN THE BOX XG36-JIB User Manual

Page 12

Advertising
background image

Part # JIBSM08 Rev 7 (08/04/09)

Page 12

4. Insert loose wires and strain relief cord end through

the hole at the bottom of the unit. Refer to photo F and

secure with locknut. Refer to photo E.

Photo F

5. Attached wire ends to terminal block as shown in next

section and referenced in wiring diagrams at back of this

manual.

6. Reinstall the side panel and grease bucket support with

metal screws. The external electrical connection should

appear as in photo G.

Photo G

Electrical Connection

Terminal Block Connection

All electrically operated appliances must be electrically

grounded in accordance with local codes; or in the absence

of local codes, with the latest edition of National Wiring

Regulations. A wiring diagram is located behind the rear

panel of the grill. See rating plate in rear of grill, or lower front

panel for proper voltages.

Note: see diagram below for connections to terminal block.

Green-Ground

White - Z

Black - Y

Red - X

Wire leads from

Cord and Plug

Main Terminal

Block of Grill

G

Z

Y

X

Grease Bucket:

The griddle is supplied with two stainless steel side grease

buckets that must be installed before the unit is used. Each

bucket slides into position along stainless steel supports.

Ventilation and Clearance:

One of the most important considerations for efficient grill

operation is proper ventilation and air supply. Insure the

grill is installed so the products of combustion are removed

efficiently and the ventilation system does not produce

drafts that interfere with proper burner operation.

Proper operation of exhaust fans (speed, rotation and

adjustment) is essential. In addition to the exhaust system

the make-up air system, (HVAC), for the kitchen is the

air supply for the combustion air for the burners. Proper

incoming air is essential for all gas operated equipment. Poor

incoming make-up will cause inefficient burner operation,

delayed ignition and possible burner failure.

Any ventilation system will break down if improperly

maintained. The duct system, the hood, and the filters must

be cleaned on a regular basis and kept grease free.

The room containing the grill is required to have a

permanent air vent. The minimum effective area of the vent

shall be 0.7 in.² per kW. Air vents shall be of such a size to

compensate for the effects of any extract fan in the premises.

Changing to a different type of gas

Changing from one gas type to another must only be

done by a Qualified Gas Engineer and according to local

regulations.

UNIT INSTALLATION

continued

Advertising
This manual is related to the following products: