Unit installation – Garland JACK IN THE BOX XG36-JIB User Manual

Page 9

Advertising
background image

Part # JIBSM08 Rev.6 (08/04/09)

Page 9

UNIT INSTALLATION

Rating Plate Location

IMPORTANT: Rating plates for this appliance are located in

two places: 1) inside back panel on left side, 2) under front

control panel on center .

General Information

This equipment must be installed by a competent factory

trained, certified, licensed and / or authorized service or

installation person.

WARNING: This appliance must be properly grounded.

Prior to installation, the four casters, supplied loose with the

grill, must be securely located on the underside of the base.

The casters fitted with a brake must be located at the front of

the grill.

This appliance should be connected to a potential

equalization system. A labeled equipotential bonding point

is fitted to the rear of the grill.

It is recommended that this grill be connected to a residual

current (earth leakage) device with a tripping current not

exceeding 30mA. The leakage current of this grill will not

exceed 5mA.

CAUTION: Prior to installation, check the electrical supply

to ensure input voltage and phase match the equipment

voltage rating and phase. See data plate located rear left side

of grill and lower front panel.

Grill is to be located directly under ventilation system.

Once installed in the grill station underneath the ventilation

system, the platens, in their highest position, must not

interfere with the lower lip of the ventilation system hood.

The raised position of each platen is adjusted by raising

or lowering the upper of the two microswitches, (limit

switches), in the rear of the grill. The lower microswitch

position must not be adjusted.

Grill plate must be level front to back, side to side and

diagonally. This leveling must be done with the unit under

the hood and in it’s normal operational position to prevent

warping of the grill plate.

NOTE: Once the platen elevation is adjusted, set the

mechanical over-run bolts in the rear of the unit to prevent

accidental over-run in the event of failure of the upper

microswitch.

NOTE: Fuses are installed to prevent damage in the event of

failure of the upper microswitch.

Installation shall be made with the gas connector that has

been specified by The Jack in the Box Corporation and is

supplied loose with the grill. The quick disconnect fitting and

gas shut off valve must be installed in the direction indicated

on their outer body.

NOTE: When checking gas pressure, be sure that all other

equipment on the same gas line is on .

The appliance and its individual shut-off valve must be

disconnected from the gas supply piping system during any

pressure testing of that system pressures in excess of 1/2

PSIG (3.45kPa, 14”WC).

Adequate clearance must be provided for servicing and

proper operation.

National Codes Requirements:

The type of gas for which the grill is equipped is stamped on

the data plate on the inside rear of the unit and on the lower

front panel. Connect a grill stamped for Natural Gas (High (H)

or Low (L) Calorific Value) only to Natural Gas; connect those

stamped for Propane Gas only to Propane gas.

The installation must conform to the National Fuel Gas Code

ANSI Z223.1-1998 or latest edition, NFPA No. 54 – latest

edition and National Electrical Code ANSI/NFPA 70-1990 or

latest edition and/or local code to assure safe and efficient

operation. In Canada, the installation must comply with CSA

B149.1 and local codes where applicable.

In Canada, electrical connection must comply with

applicable sections of the Canadian Electrical Code, C22.1

- 1990, latest edition, “Safety Standard for Installation,

Part 1” and C22.2- No. O-M 1982 latest edition , “General

Requirements, Part 2”.

Gas Connections, and Pipe Sizing:

The size of the gas line is very important. If the line is too

small, the gas pressure at the burner manifold will be low.

This will cause slow recovery and delayed ignition. The

incoming gas pressure line should be a minimum of 1-1/2".

All grills require a 3/4" connection.

Before connecting new pipe the pipe must be blown out to

dispose of any foreign particles. These particles will cause

improper operation.

When using thread compound, use small amounts on male

threads only. Use a compound that is not affected by the

chemical action of LP gases. Avoid applying compound

to the first two threads to prevent clogging of the burner

orifices and control valve.

Have the installer check all gas plumbing with a soap

solution for leaks. DO NOT USE matches, candles or other

ignition sources in checking for leaks.

Advertising
This manual is related to the following products: