Specifications – Sanyo KHH2672R / CH2672R User Manual

Page 103

Advertising
background image

I-99

SM831148

1. Specifications

1

2

3

4

5

6

Indoor Unit

Control Wiring

Type

(B) Power Supply

AWG #14

(C) Inter-Unit Control Wiring

(D) Remote Control Wiring

(E) Control Wiring For Group Control

Trade Size

of Conduit

MOP

(Fuse or HACR

type circuit breaker)

AWG #18

Use high voltage wire (300 V)

*1

AWG #18

*2

(0.75 mm

2

)

Max. 1,650 ft.

Max. 3,300 ft.

Max. 1,650

ft. (Total)

AWG #18

*2

(0.75 mm

2

)

3/4 in.

15 A

Max. length 67 ft.

X, K, T, U

*1

With ring-type wire terminal.

*2

Wire joint connection.

Wiring System Diagrams

Basic wiring diagram for standard control

NOTE

1) Refer to “

Recommended Wire Length and Wire

Diameter for Power Supply System” for the explana-
tion of “A”, “B”, “C”, “D”, and “E”, in the above dia-
grams.

2) Inter-Unit Control Wiring (C) and remote controller

wiring (D), (E) have no polarity. But for other wiring,
respect polarity. Be sure to connect as shown in the
Wiring System Diagram.

3) In case of separate supply connection to indoor unit,

over current protection must be provided between
power source and indoor unit.

MAXIMUM OVER CURRENT PROTECTION 15 A
(FUSE OR HACRTYPE CIRCUIT BREAKER)

U2

U1

L1

L2

U1

U2

1

2

G

2

1

WHT

Remote
controller

D

A

Indoor

unit

B

L1
L2

Grounding line

BLK

2

1

Inter-unit power line
208 / 230 V, 60 Hz

Power supply
208 / 230 V, 60Hz

Grounding line

C

Ground

Outdoor unit

INV unit

1

2

G

G

Inter-unit

power wiring

U1

Inter-unit

control wiring

U2

5P terminal board

X, T, U Type

Remote

controller wiring

Inter-unit

control wiring

4P terminal board

G

Inter-unit

power wiring

U1 U2

K Type

Inter-unit

power wiring

Power wiring

Inter-unit

control wiring

8P terminal board

CH Type

U1 U2

L2

1 2 G L1

1 2

Remote

controller wiring

1

2