Sanyo KHH2672R / CH2672R User Manual

Page 30

Advertising
background image

1

2

3

4

5

6

I-26

SM831148

1. Specifications

1-1 Unit Specifications

Ceiling-Mounted Type

Indoor Unit

TH4272R

Outdoor Unit

C4272R

POWER SOURCE

230 - 208 V / 1 Phase / 60 Hz

PERFORMANCE

Cooling

Capacity * [minimum~muximum]

BTU / h

39,000 [9,500~39,000]

(17˚F)**

BTU / h

Moisture removal (High)

Pints / h

12.6

Air circulation (H / M / L) 230 V

CFM

1100 / 930 / 750

External Static Pressure

in. WG

S.E.E.R. / H.S.P.F. (Region 4)

BTU / Wh

15.6

ELECTRICAL RATINGS

Voltage rating

V

230

208

Available voltage range

V

VAC 187 - 253

Max. Running amperes*

A

21.1

23.3

Power input

W

4,140

4,140

(17˚F)**

W

Back-up Heater

kW

Maximum overcurrent protection (Indoor/Outdoor)

A

15 / 40

Controls

Microprocessor

Low ambient control

Built-in 0˚F

Fan speeds Indoor / Outdoor

3 and Automatic control / Variable

Optional Wired Remote Controller
Optional Wireless Remote Controller

RCS-SH80UA. WL / RCS-BH80UA. WL

Air deflection (Horizontal / Vertical )

/ Automatic (Vertical )

Air filter

Washable, long life (2,500 hr)

Drain pump (Drain connection)

(20A , OD26mm)

Compressor

Rotary(SANYO)

Operation sound

Indoor - Hi/Me/Lo

dB - A

44 / 41 / 37

Outdoor - Hi

dB - A

53

Refrigerant control

Electronic Expansion Valve (MOV)

REFRIGERANT TUBING

Limit of tubing length

ft. (m)

165 (50)

Limit of tubing length at shipment

ft. (m)

10~100 (3~30)

Limit of elevation difference

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

between the two units

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

Refrigerant tube

Narrow tube

in. (mm)

3 / 8 (6.35)

outer diameter

Wide tube

in. (mm)

5 / 8 (15.88)

Refrigerant amount at shipment

lbs. (kg)

7.94 (3.6) - R410A

DIMENSIONS & WEIGHT

Indoor unit

Outdoor unit

Unit dimensions

Height

in. (mm)

9-7/16 (240)

48-7/16 (1,230 )

Width

in. (mm)

62-1/32 (1,575)

37 (940)

Depth

in. (mm)

26-3/8 (670)

13- 3/8 (340)

Package dimensions

Indoor unit

Outdoor unit

Height

in. (mm)

12-15/32 (317)

52-3/8 (1,330 )

Width

in. (mm)

66-1/16 (1,678)

39- 31/32 (1,015)

Depth

in. (mm)

31-1/16 (789)

16- 3/32 (409)

Net weight

lbs. (kg)

84 (38)

220 (100)

Shipping weight

lbs. (kg)

97 (44)

240 (109 )

Shipping volume

cu.ft. (m 3 )

14.8 (0.420)

19.5 (0.552 )

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

FEATURES

MODEL No.

RCS-SH80UG / RCS-TM80BG

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

Advertising