6. Test run

Indicating (marking) the indoor and outdoor unit combination number

Indicate (mark) the number after automatic address setting is completed.

(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that

the indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB,
and use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily
visible location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 - (Indoor) 1-1...(Outdoor) 2 - (Indoor) 2-2...

(2) These numbers will be needed for maintenance. Be sure to indicate them.

*

Use the remote controller to check the addresses of the indoor units. Press and hold the button and
button for 4 seconds or longer (simple settings mode). Then press the button

and select the indoor

address. (Each time the button is pressed, the address changes as follows: 1-1, 2-1, ....) The indoor unit fan
operates only at the selected indoor unit. Confirm that correct fan is operating, and indicate address on the
indoor unit.

Press the button again to return to the normal remote controller mode.

For details, refer to the separate handbook.

Main-sub remote controller control

Control using 2 remote controller switches

Main-sub remote controller control refers to the use of 2 remote controllers to control 1 indoor unit.
(A maximum of 2 remote controllers can be connected.)

Connecting 2 remote controllers to
control 1 indoor unit

(Setting procedure)

(1) Set 1 of the 2 connected remote controllers as the

main remote controller.

(2) On the other remote controller (sub remote controller),

change the remote controller address connector on the
reverse side of the remote controller switch PCB from
the Main position to the Sub position.
The remote controller will now function as the sub
remote controller.

1 2

1 2

1 2

U1U2

1 2

Remote controller wiring

Optional

Optional

Remote controller
switch (sub)

Remote controller
switch (main)

Indoor unit

Outdoor unit

Ground

Ground

for remote
controller wiring

Terminal plate

Fig. 6-8

Remote controller

Remote controller
address connector

RCU. ADR

Main

Sub

RCU check