1. Specifications

1-2 Major Component Specifications

(A) Indoor Unit

MODEL No.

XH4272R

Source

230 - 208 VAC / 1 phase / 60 Hz

Remote controller (Option)

Wired or Wireless (See Unit Specification)

Controller P. C. B Ass'y

CR - TH2672

Control circuit fuse

250 VAC, 5 A

Fan (Number … diameter)

in.

(mm)

Turbo (1…17-7/16 (443))

Fan motor

Model

SFG6X - 81A6P

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole … r.p.m. (230 V, High)

rpm

6 … 506

Nominal output

W

60

Coil resistance

BRW - WHT

:

75.1

,

ORG - YEL

:

27.4

(Ambient temperature 68

°F)

WHT - VLT

:

6.7

,

VLT

- PNK

:

42.7

VLT

- ORG

:

20.6

,

YEL

- BLK

:

58.0

Safety device

Operating temperature

Open

°F

266

± 14.4

Close

°F

174.2

± 27

Run capacitor

VAC,

µF

440 V , 6

µF

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows … Fins per inch

2 … 14.9

Face area

ft.

2

(m

2

)

8.20 (0.762)

Panel

Model No.

PNR - XH3642

Auto louver motor

MT8 - 3C

Auto louver motor … Rated

V, W,

rpm

240 VAC , 3 W , 3 rpm

Coil resistance (Ambient temperature 77

°F)

16.430

Ω ± 8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE