Sanyo KHH2672R / CH2672R User Manual

Page 20

Advertising
background image

1

2

3

4

5

6

I-16

SM831148

1. Specifications

1-1 Unit Specifications

Concealed-Duct Type

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

Indoor Unit

UH3672R

Outdoor Unit

CH3672R

POWER SOURCE

230 - 208 V / 1 Phase / 60 Hz

PERFORMANCE

Cooling

Heating

Capacity * [minimum~muximum]

BTU / h

31,200 [9,500~31,200]

36,200 [8,000~36,200]

(17˚F)**

BTU / h

20,200

Moisture removal (High)

Pints / h

10.0

Air circulation (H / M / L) 230 V

CFM

670 / 530 / 460

External Static Pressure

in. WG

0.24:at shipment / 0.4:using jumper cable

S.E.E.R. / H.S.P.F. (Region 4)

BTU / Wh

13.9

8.7

ELECTRICAL RATINGS

Voltage rating

V

230

208

230

208

Available voltage range

V

VAC 187 - 253

VAC 187 - 253

Max. Running amperes*

A

18.6

20.6

15.9

17.6

Power input

W

3,920

3,920

3,340

3,340

(17˚F)**

W

2,570

2,570

Back-up Heater

kW

Maximum overcurrent protection (Indoor/Outdoor)

A

15 / 35

Controls

Microprocessor

Low ambient control

Built-in 0˚F

Fan speeds Indoor / Outdoor

3 and Automatic control / Variable

Optional Wired Remote Controller
Optional Wireless Remote Controller

RCS-BH80UA. WL

Air deflection (Horizontal / Vertical )
Air filter
Drain pump (Drain connection)

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

Compressor

Rotary(SANYO)

Operation sound

Indoor - Hi/Me/Lo

dB - A

38 / 33 / 31

Outdoor - Hi

dB - A

52

Refrigerant control

Electronic Expansion Valve (MOV)

REFRIGERANT TUBING

Limit of tubing length

ft. (m)

165 (50)

Limit of tubing length at shipment

ft. (m)

10~100 (3~30)

Limit of elevation difference

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

between the two units

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

Refrigerant tube

Narrow tube

in. (mm)

3 / 8 (6.35)

outer diameter

Wide tube

in. (mm)

5 / 8 (15.88)

Refrigerant amount at shipment

lbs. (kg)

6.17 (2.8) - R410A

DIMENSIONS & WEIGHT

Indoor unit

Outdoor unit

Unit dimensions

Height

in. (mm)

12-7/32 (310)

30- 23/32 (780)

Width

in. (mm)

58-9/32 (1,480)

37 (940)

Depth

in. (mm)

24-13/16 (630)

13- 3/8 (340)

Package dimensions

Indoor unit

Outdoor unit

Height

in. (mm)

14-3/32 (358)

34- 31/32 (888)

Width

in. (mm)

65-25/32 (1,671)

39- 31/32 (1,015)

Depth

in. (mm)

30-13/16 (783)

16- 3/32 (409)

Net weight

lbs. (kg)

104 (47)

143 (65)

Shipping weight

lbs. (kg)

115 (52)

161 (73)

Shipping volume

cu.ft. (m 3 )

16.5 0.468)

13.0 (0.369)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

FEATURES

MODEL No.

RCS-SH80UG / RCS-TM80BG

Advertising