Sanyo KHH2672R / CH2672R User Manual

Page 14

Advertising
background image

1

2

3

4

5

6

I-10

SM831148

1. Specifications

1-1 Unit Specifications

4-Way Air Discharge Semi-Concealed Type

Cooling:

Rating conditions (*) : Room temperature 80 °F DB / 67 °F WB, Ambient temperature 95 °F DB / 75 °F WB

Heating:

Rating conditions (*) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 47 °F DB / 43 °F WB
Low temp conditions (**) : Room temperature 70 °F DB / 60 °F WB, Ambient temperature 17 °F DB / 15 °F WB

Indoor Unit

XH3672R

Outdoor Unit

CH3672R

POWER SOURCE

230 - 208 V / 1 Phase / 60 Hz

PERFORMANCE

Cooling

Heating

Capacity * [minimum~muximum]

BTU / h

32,600 [9,500~32,600]

37,600 [8,000~37,600]

(17˚F)**

BTU / h

20,000

Moisture removal (High)

Pints / h

10.6

Air circulation (H / M / L) 230 V

CFM

1050 / 840 / 720

External Static Pressure

in. WG

S.E.E.R. / H.S.P.F. (Region 4)

BTU / Wh

14.6

9.1

ELECTRICAL RATINGS

Voltage rating

V

230

208

230

208

Available voltage range

V

VAC 187 - 253

VAC 187 - 253

Max. Running amperes*

A

18.7

20.7

15.9

17.6

Power input

W

3,950

3,950

3,350

3,350

(17˚F)**

W

2,450

2,450

Back-up Heater

kW

Maximum overcurrent protection (Indoor/Outdoor)

A

15 / 35

Low ambient control

Built-in 0˚F

Fan speeds Indoor / Outdoor

3 and Automatic control / Variable

Optional Wired Remote Controller
Optional Wireless Remote Controller

RCS-SH80UA. WL / RCS-BH80UA. WL

Air deflection (Horizontal / Vertical )

/ Automatic (Vertical )

Air filter

Washable, long life (2,500 hr)

Drain pump (Drain connection)

Max.head 2-33/64 in. above drain connection (25A , OD32mm)

Compressor

Rotary(SANYO)

Operation sound

Indoor - Hi/Me/Lo

dB - A

44 / 37 / 33

Outdoor - Hi

dB - A

52

Refrigerant control

Electronic Expansion Valve (MOV)

REFRIGERANT TUBING

Limit of tubing length

ft. (m)

165 (50)

Limit of tubing length at shipment

ft. (m)

10~100 (3~30)

Limit of elevation difference

ft. (m)

Outdoor unit is higher than indoor unit : 100 (30)

between the two units

ft. (m)

Outdoor unit is lower than indoor unit : 50 (15)

Refrigerant tube

Narrow tube

in. (mm)

3 / 8 (6.35)

outer diameter

Wide tube

in. (mm)

5 / 8 (15.88)

Refrigerant amount at shipment

lbs. (kg)

6.17 (2.8) - R410A

DIMENSIONS & WEIGHT

Indoor unit (Include panel)

Outdoor unit

Unit dimensions

Height

in. (mm)

14-31/64 (368)

30- 23/32 (780)

Width

in. (mm)

45-9/32 (1,150)

37 (940)

Depth

in. (mm)

33-55/64 (860)

13- 3/8 (340)

Package dimensions

Body

Panel

Outdoor unit

Height

in. (mm)

12-13/32 (315)

4-3/32 (104)

34- 31/32 (888)

Width

in. (mm) 44-19/64 (1,125) 49-31/64 (1,257) 39- 31/32 (1,015)

Depth

in. (mm)

33-9/32 (845)

39-21/64 (999)

16- 3/32 (409)

Net weight

lbs. (kg)

60 (27)

16 (7)

143 (65)

Shipping weight

lbs. (kg)

71 (32)

22 (10)

161 (73)

Shipping volume

cu.ft. (m 3 )

10.6 (0.299)

4.6 (0.131)

13.0 (0.369)

DATA SUBJECT TO CHANGE WITHOUT NOTICE.

FEATURES

MODEL No.

Controls

Microprocessor

RCS-SH80UG / RCS-TM80BG

Advertising