Sanyo KHH2672R / CH2672R User Manual

Page 91

Advertising
background image

I-87

SM831148

1. Specifications

1

2

3

4

5

6

Table 1-2 Tubing Data for Models

Limit of elevation

difference between

the 2 units

Models

C(H)2672R

C(H)3072R
C(H)3672R

C(H)4272R

Tubing Data

Tubing size

Liquid tube

in. (mm)

3/8 (9.52)

3/8 (9.52)

3/8 (9.52)

outer diameter

Gas tube

in. (mm)

5/8 (15.88)

5/8 (15.88)

5/8 (15.88)

Limit of tubing length

(ft.)

165

165

165

Outdoor unit is placed

100

100

100

higher

(ft.)

Outdoor unit is placed

50

50

50

lower

(ft.)

Max. allowable tubing length at shipment (ft.)

10 – 100

10 – 100

10 – 100

Required additional refrigerant *

1

(oz./ft.)

a) 0.43

b) 0.43

b) 0.43

Refrigerant charged at shipment

(lbs.)

4.2

6.2

7.9

No additional charge of compressor oil is necessary.
*1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft.

Table 1-3 List of Connection Tube Sizes

26 – 42

ш

5/8"

ш

3/8"

0.43 oz.

Gas tube

Liquid tube

Main tubing (L)

Type capacity of indoor units

Amount of additional charge per 1 ft.

Advertising