Sanyo KHH2672R / CH2672R User Manual

Page 40

Advertising
background image

1

2

3

4

5

6

I-36

SM831148

1. Specifications

1-2 Major Component Specifications

(A) Indoor Unit

MODEL No.

UH3672R

Source

230 - 208 V / 1 phase / 60 Hz

Remote controller (Option)

Wired or Wireless (See Unit Specification)

Controller P. C. B Ass'y

CR - TH2672

Control circuit fuse

250 V, 5 A

Fan (Number … diameter)

in.

(mm)

Centrifugal (4 ... 5-29/32(150))

Fan motor

Model

KFG4X - 141A6P

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole ... r.p.m. (230 V, High)

rpm

4 ... 940

Nominal output

W

100

Coil resistance

BRW - WHT

:

39.9

,

ORG - YEL

:

9.37

(Ambient temperature 68

°F)

WHT - VLT

:

6.91

,

YEL

- BLK

:

8.86

VLT

- ORG

:

11.4

,

BLK

- PNK

:

14.3

Safety device

Operating temperature

Open

°F

266

± 14.4

Close

°F

174.2

± 27

Run capacitor

VAC,

µF

440 V , 5

µF

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows ... Fins per inch

3 ... 12.7

Face area

ft.

2

(m

2

)

3.32 (0.308)

DATA SUBJECT TO CHANGE WITHOUT NOTICE