Sanyo KHH2672R / CH2672R User Manual

Page 64

Advertising
background image

1

2

3

4

5

6

I-60

SM831148

1. Specifications

1-3 Other Component Specifications

(B) Outdoor Unit

MODEL No.

CH2672R, C2672R

Thermistor (Coil sensor) : TH2 to 5

Coil resistance

k

14

°F : 23.7

,

50

°F : 9.7

23

°F : 18.8

,

68

°F : 6.5

32

°F : 15.0

,

86

°F : 4.4

41

°F : 12.1

,

104

°F : 3.1

113

°F : 2.6

Thermistor (Comp. discharge gas sensor) : TH6

Coil resistance

k

140

°F : 13.8

,

194

°F : 5.1

158

°F : 9.7

,

212

°F : 3.8

167

°F : 8.2

,

230

°F : 2.8

176

°F : 7.0

,

248

°F : 2.2

185

°F : 5.9

,

266

°F : 1.7

Solenoid coil or 4 way valve

4 way valve

STF - 02UG

Solenoid coil

STF - 01AQ503UA1 (Heat pump model only)

DATA SUBJECT TO CHANGE WITHOUT NOTICE

Electric expansion valve (MOV)

Valve

UKV - 18D13

Coil

UKV - U013E

Advertising