Sanyo KHH2672R / CH2672R User Manual

Page 35

Advertising
background image

1

2

3

4

5

6

I-31

SM831148

1. Specifications

1-2 Major Component Specifications

(A) Indoor Unit

MODEL No.

TH3672R

Source

230 - 208 V / 1 phase / 60 Hz

Remote controller (Option)

Wired or Wireless (See Unit Specification)

Controller P. C. B Ass'y

CR - TH2672

Control circuit fuse

250 V, 5 A

Fan (Number … diameter)

in.

(mm)

Centrifugal (4 ... 5-29/32(150))

Fan motor

Model

KFG4X - 101C6P

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole … r.p.m. (230 V, High)

rpm

4 ... 1,040

Nominal output

W

100

Coil resistance

BRW - WHT

:

61.05

,

ORG - YEL

:

13.23

(Ambient temperature 68

°F)

WHT - VLT

:

9.955 ,

YEL

- BLK

:

19.25

VLT

- ORG

:

9.576 ,

BLK

- PNK

:

10.81

Safety device

Operating temperature

Open

°F

266

± 14.4

Close

°F

174.2

± 27

Run capacitor

VAC,

µF

440 V , 4

µF

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows … Fins per inch

3 … 14.9

Face area

ft.

2

(m

2

)

3.51 (0.326)

Auto louver motor

Model No.

MT8 - 3C

Auto louver motor … Rated

V, W, rpm

240 VAC , 3 W , 3 rpm

Coil resistance (Ambient temperature 77

°F)

16,430

Ω ± 8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE