Sanyo KHH2672R / CH2672R User Manual

Page 93

Advertising
background image

I-89

SM831148

1. Specifications

1

2

3

4

5

6

Fig. 1-4

Anchor bolts
(4 pieces)

Fig. 1-1

Out-
door
unit

Heat source

Hot air

Exhaust fan

*4

*2

*3

*1

More than 25/64"

More than
3.3 ft.

More than 25/64"

Inlet side C

Outlet side

Fig. 1-2

Fig. 1-3

*1

Inlet side
More than 8"

(field supply)

A

B

(Ground)

Air direction chamber

(Obstruction above unit)

(Obstruction on
inlet side)

CAUTION

Concerning inlet-side distance “C” (Fig. 1-2)

The minimum for distance “C” is 6" if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
“C” is 8".

If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.

If wall *1 is on the outlet side (Fig. 1-2), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 1-2), then the minimum distance for “A” and “B” is 80" (Fig. 1-3). Even if
there is no wall on the outlet side, a minimum of 3.3 ft. is required.

Installation requirements

provide a solid base (concrete block, 4" × 16"
beams or equal), a minimum of 6" above ground
level to reduce humidity and protect the unit gainst
possible water damage and decreased service life.
(Fig. 1-4)

use lug bolts or equal to bolt down unit, reducing
vibration and noise.

Outdoor Unit

AVOID:

heat sources, exhaust fans, etc. (Fig. 1-1)

damp, humid or uneven locations

DO:

choose a place as cool as possible.

choose a place that is well ventilated and outside air
temperature does not exceed maximum 115°F
constantly.

allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 1-2)

use lug bolts or equal to bolt down unit, reducing
vibration and noise.

if cooling operation is to be used when the outdoor
air temperature is 23°F or below, install a duct on the
outdoor unit.

Installation space

Distance between obstructions and the unit air inlet and
outlet must be as shown below.