Sanyo KHH2672R / CH2672R User Manual

Page 37

Advertising
background image

1

2

3

4

5

6

I-33

SM831148

1. Specifications

1-2 Major Component Specifications

(A) Indoor Unit

MODEL No.

THH2672R

Source

230 - 208 V / 1 phase / 60 Hz

Remote controller (Option)

Wired or Wireless (See Unit Specification)

Controller P. C. B Ass'y

CR - TH2672

Control circuit fuse

250 V, 5 A

Fan (Number ... diameter)

in.

(mm)

Fan motor

Model

Source

No. of pole ... r.p.m. (230 V, High)

rpm

1,187

Nominal output

W

31

Coil resistance

(Ambient temperature 68

°F)

Safety device

Operating temperature

Open

°F

266

± 14.4

Close

°F

174.2

± 27

Run capacitor

VAC,

µF

440 V , 1.5

µF

Heater Ass'y (Aux. Heater)

Model

AH - 1.8THS2432

1.8 / 1.45

Input (230 / 208 V)

KW

Protective thermostat

CS- 12AL OFF 122

± 6°F, ON 104 ± 10°F

Thermo fuse

SF96U Cut - off 205

± 4°F

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows ... Fins per inch

3 ... 14.9

Face area

ft.

2

(m

2

)

1.81 (0.168)

Auto louver motor

Model No.

MT8 - 3C

Auto louver motor ... Rated

V, W, rpm

240 VAC , 3 W , 3 rpm

Coil resistance (Ambient temperature 77

°F)

16,430

Ω ± 8 %

DATA SUBJECT TO CHANGE WITHOUT NOTICE

BRW - WHT

:

111.0

,

ORG - YEL

:

16.7

WHT - VLT

:

35.4

,

BLK

- PNK

:

23.9

VLT

- ORG

:

13.4

,

YEL

- BLK

:

136.6

Centrifugal (4 ... 5-1/8(130))

SR4X - 51A6P

230 - 208 V / 1 phase / 60 Hz