2. Processes and functions

1





2

3

Defrost control

Defrost sequence

Heating operation

(25-minute mask)

Frost detection

Defrost start

(reverse cycle defrost)

Defrost in progress

Defrost cancel

Start-up operation

Operating frequency: 61.8 Hz
Outdoor unit fan: OFF
Electronic control valve: step 300
4-way valve: OFF
Indoor unit fan: OFF

Defrost control

(1) Frost detection

1. Outdoor heat exchanger temperature (C1) method (15-minute mask after operation start)

2. Outdoor air temperature is 7°F or above and outdoor heat exchanger temperature (C1) of 0°F or below is

detected continuously for 20 seconds.

3. Outdoor air temperature is below 7°F and outdoor heat exchanger temperature (C1) of below (outdoor air

temperature -10)°F is detected continuously for 20 seconds.

(2) Defrost cancel

• Defrost end conditions

1. Outdoor heat exchanger temperature (C1) rises to 54°F or higher.
2. Outdoor heat exchanger temperature is 45°F or higher continuously for 1 minute.
3. Defrost time of 10 minutes has elapsed.

(3) Startup operation
After defrost ends, the compressors and outdoor unit fan stop for approximately 40 seconds, then operation begins
in heating mode.