4. Service procedures

1

2

3

4

5

6

No

No

No

No

Yes

Yes

Yes

Yes

(4) [Alarm "P22"]

Outdoor unit fan motor drive circuit trouble

Are connectors CN003 and CN004 connected

correctly to the outdoor unit control PCB?

Correct the connector

connections.

Disconnect connectors CN003 and CN004

from outdoor unit control PCB, and rotate

fan by hand. Does it rotate easily?

Outdoor unit fan motor coil resistance is
OK if it is as shown below.

(1) Red – white: 30 – 40

(2) White – black: 30 – 40

(3) Black – red: 30 – 40

* Disconnect connector CN004 and
measure on the plug side.

Motor position detection circuit resis-
tance is OK if it is as shown below.

* Disconnect connector CN003 and measure
on the plug side.

(1) Grey – yellow: 100 k

Ω or more, or

(open)

(2) Grey – blue:

100 k

Ω or more, or

(open)

(3) Grey – orange: 100 k

Ω or more, or

(open)

Fan motor is OK; outdoor unit

control PCB has failed.

→ Replace.

Fan motor trouble

→ Replace.

Note:
In the case of a GND circuit failure inside the motor, the results
of the above check may be OK.
If operation is not OK after the outdoor unit control PCB has
been replaced, then replace the outdoor unit fan motor.