1. Specifications

1-2 Major Component Specifications

(A) Indoor Unit

MODEL No.

KH2672R

Source

230 - 208 V / 1 phase / 60 Hz

Remote controller (Option)

Wired or Wireless (See Unit Specification)

Controller P. C. B Ass'y

CB - KR24GXH56A

Control circuit fuse

250 V, 5 A

Fan

Cross-flow

Number ... Dia. and length

in.

(mm)

1 ... O.D. 4-1/3 (110), L39 (990)

Fan motor

Model

KFT4Q - 31A6P - C

Source

230 - 208 V / 1 phase / 60 Hz

No. of pole ... r.p.m. (230 V, High)

rpm

4 ... 1,224

Nominal output

W

28.8

Coil resistance

BRW - WHT

:

260.7

,

ORG - YEL

:

23.76

(Ambient temperature 68

°F)

WHT - VLT

:

42.62

,

YEL

- PNK

:

115.9

VLT

- ORG

:

30.36

,

Safety device

Operating temperature

Open

°F

±

14.4

Close

°F

174.2

± 26

Run capacitor

VAC,

µF

440 V , 1.8

µF

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows ... Fins per inch

2 ... 24.1

Face area

ft.

2

(m

2

)

2.57 (0.24)