2.symptoms and parts to inspect, Service procedures, 2. symptoms and parts to inspect – Sanyo KHH2672R / CH2672R User Manual

Page 151

Advertising
background image

IV-5

SM831148

4. Service procedures

1

2

3

4

5

6

4-2. Symptoms and Parts to Inspect

Judgment condition

Clear condition

P03

P05

P04

P15

P19

P20

P22

P26

Remote

controller

alarm display

Alarm

contents

Judgment and

correction

Abnormal discharge
temperature

• Discharge temp.

detected at or
above the specified
value.

Stops when temp. exceeds
232 ˚F.

Recovery at restart

Recovery at restart

Recovery at restart

Recovery at restart

Recovery at restart

Recovery at restart

Recovery at restart

Recovery at restart

1. Check refrigerant cycle

(gas leak).

2. Electronic control valve

trouble

3. Check tubing sensor (TD).

Missing phase

High pressure
switch is activated.
Compressor motor
thermal protector is
activated.

detected. (CT
disconnected or AC
power trouble)

Current value sent from MDC

Stops when pressure
exceeds 600 psi.
Stops when temp. exceeds
230 ˚F.

on outdoor unit control PCB is
low.
No AC power input for 3
minutes or longer: pre-trip - 5

1. Check R/S/T power.
2. Check inverter control PCB.
3. Check outdoor unit control

PCB.

Insufficient gas level
detected.

The following conditions
continue for 1 minute.
• Discharge temp. is 203 ˚F or

higher.

• Electronic control valve is at

step 480.

• Current value from MDC is

2.0 A or less.

Check refrigerant cycle
(gas leak).

4-way valve locked
• Judgment occurs

after compressor
has been ON for 5
minutes.

Indoor heat exchanger temp.
drops although compressors
are ON in heating mode:
[min(E1, E2)]

≤ 50 ˚F.

Indoor heat exchanger temp.
rises although compressors are
ON in cooling mode:
E2

≥ 104 ˚F.

1. Check 4-way valve.
2. Check 4-way valve wiring.
3. Check outdoor unit control

PCB.

High-pressure
protection trouble

1. Refrigerant cycle

overload operation

2. Outdoor coil temperature

sensor C1 or C2

Outdoor unit fan
motor trouble
• Inverter protection

circuit was
activated, or lock
was detected, at
outdoor unit fan
motor.

Inverter stops after alarm is
detected

1. Position detection trouble
2. Overcurrent protection

circuit at outdoor unit fan
motor was activated.
• Check outdoor unit control

PCB.

• Refer to outdoor unit fan

judgment methods.

Inverter protection
circuit was
activated, or G-Tr
short-circuit (short
time: 0.8 s or less)
in inverter control

Inverter stops after alarm is
detected. Alarm is output
when inverter stops (pre-trip)
consecutively 4 times.

1. Stops immediately when

restarted.
• Layer short in the

compressor

2. Check inverter control

PCB.
• Wiring trouble

1. Check the high pressure

switch connector is
securely connected.

2. Check the ourdoor unit heat

exchanger is not clogged
(cooling operation).

3. Check the indoor unit air

filter has not become
clogged (heating operation)

If MAX (C1,C2) is 142

°F or

higher, the compressor stops
one. The compressor restarts
three time, and if the
temperature does not
decrease to less than 142

°F,

the alert “P20” is displayed.

Advertising