2.caution, 3.test run procedure – Sanyo KHH2672R / CH2672R User Manual

Page 173

Advertising
background image

VI-3

SM831148

1

2

3

4

5

6

6. Test run

X, T, U, K Type

6-2. Caution

This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit.

The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings
required for operation were made at the time of shipment.
Only the correct combination of indoor and outdoor units can be used.

This test run manual describes primarily the procedure when using the wired remote controller.

6-3. Test Run Procedure

Recheck the items (see IV-4) to check before the test run.

Turn ON the indoor and outdoor power.

Set the remote controller to “test run.”

Return the remote controller to normal
control.

YES

NO

Automatic

address?

(See I-98)

(See VI-4)

Check the combination (wiring) of indoor and
outdoor units.

Refer to “Table of Self-Diagnostic
Functions and Corrections” to
check the system.

YES

NO

Note: Check the indoor-side drainage.

Has the

test run been

completed?

Check the warning code.

Fig. 6-3

Advertising