11.installation instructions – Sanyo KHH2672R / CH2672R User Manual

Page 90

Advertising
background image

1

2

3

4

5

6

I-86

SM831148

1. Specifications

1-11 Installation Instructions

Tubing Length

Single type

Refrigerant tubing between the indoor and outdoor
units should be kept as short as possible.

The length of the refrigerant tubes between the
indoor and outdoor units are limited by the elevation
difference between the 2 units. During tubing work,
try to make both the tubing length (L) and the
difference in elevation (H1) as short as possible.
Refer to Table 1-2.

Table 1-1

Single

H1

Maximum length

H1

H1

< 100

< 50

Maximum indoor-outdoor
height difference

If outdoor unit is higher

If outdoor unit is lower

Indoor unit type

26, 30, 36 types

42 type

Maximum length

165 ft.

165 ft.

Charge-less tubing length (actual length)

10 – 100 ft.

15 – 100 ft.

Additional charge per 1 ft.

0.43 oz.