Model selecting and capacity calculator – Sanyo CHDZ09053 User Manual

Page 14

Advertising
background image

2-4

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

1. Model Selecting and Capacity Calculator

1-3. Tubing Length

H3

LM

LA

LF

LB

LC

L4

LG

LH

LD

L2

H2

L1

H1

LE

L3

C

B

4

1

2

3

5

6

7

40

1.

Main tubing length LM = LA + LB …

≤ 262 ft.

2.

Main distribution tubes LC – LH are selected according to the capacity after the
distribution joint.

3.

Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing
sizes on the indoor units.

T-joint tubing
(header joint system)

Balance tubing
(ø9.52)

Explanation of symbols

Distribution joint
(APR: purchased separately)

Solidly welded shut
(pinch weld)

Ball valve (field supply)

T-joint (field supply)

Do not use commercially available T-joints for the liquid tubing and

parts.

R410A distribution joint
APR-CHRZP900BAB (for outdoor unit)
APR-RZP224BAB (for indoor unit)
APR-RZP680BAB (for indoor unit)
APR-RZP1350BAB (for indoor unit)

* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor

unit connections and tubing branches.

For
extension

For
extension

Max. 1.3 ft.

Max. 1.3 ft.

Solenoid valve kit

NOTE

Table 2-1 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights

Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure

below.

Item

Mark

Contents

Length (ft.)

L1

Max. tubing length

Actual length

492

Equivalent length

574

ΔL (L2 – L4)

Difference between max. length and min.

131

length from the No. 1 distribution joint

LM

Max. length of main tubing (at max. diameter)

262

1

1

2

,

2

...

...

Max. length of each distribution tube

98

L1+

+

+

Total max. tubing length including length of

984

A + B+LF+LG+LH each distribution tube (only liquid tubing)

L5

L3

Distance between outdoor units

32

H1

When outdoor unit is installed higher than indoor unit

164

When outdoor unit is installed lower than indoor unit

131

H2

Max. difference between indoor units

49

H3

Max. difference between outdoor units

13

L = Length, H = Height

Allowable tubing
length

>

>

Allowable elevation
difference

>

>

>

>

>

>

>

>

>

>

*2

6.6

Allowable length of
joint tubing

T-joint tubing (field-supply); Max. tubing length between
the first T-joint and solidly welded-shut end point

40

39

NOTE

1: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for

the discharge tubes, suction tubes, and liquid tubes. (Use a fi eld supply reducer.)

2: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for

the suction tubes and discharge tubes. (Use a fi eld supply reducer.)

(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)