Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

Additional refrigerant charge before extension

Liquid tube

diameter

Tubing length (ft)

(A)

Additional refrigerant charge

per 1 ft (oz/ft) (B)

(A) × (B) oz

La

ø1/2

6.6

1.38

9.055

Lb

ø3/8

65.6

0.602

39.501

LA

ø3/4

26.2

2.78

72.966

LB

ø1/2

19.7

1.38

27.165

LC

ø1/2

19.7

1.38

27.165

LD

ø1/2

19.7

1.38

27.165

LE1

ø3/8

16.4

0.602

9.875

LG

ø5/8

26.2

1.99

52.231

LH

ø3/8

13.1

0.602

7.900

L1

ø3/8

9.8

0.602

5.925

L2

ø1/4

9.8

0.279

2.746

L3

ø1/4

9.8

0.279

2.746

L7

ø3/8

9.8

0.602

5.925

L8

ø1/4

9.8

0.279

2.746

L9

ø1/4

13.1

0.279

3.661

Total (oz)

296.775

297 oz

Additional refrigerant charge after extension

Liquid tube

diameter

Tubing length (ft)

(A)

Additional refrigerant charge

per 1 ft (oz/ft) (B)

(A) × (B) oz

LE2

ø3/8

13.1

0.602

7.900

LF

ø3/8

16.4

0.602

9.875

L4

ø3/8

13.1

0.602

7.900

L5

ø3/8

19.7

0.602

11.850

L6

ø1/4

23.0

0.279

6.407

Total (oz)

43.934

44 oz

Calculation of additional refrigerant charge for the entire 3-WAY ECO-i system

(Additional refrigerant charge for entire 3-WAY ECO-i system)
= (Refrigerant charge at outdoor unit) + (Additional refrigerant charge)
= 881 + 341 = 1222 oz (after extension)
[Before extension: 458 + 297 = 755 oz]

Remark:
When planning extension model 14053, be sure to include the values of the Table 2-1-1 (Page 2-5) Necessary Amount of
Refrigerant Charge per Unit.