W-3WAY ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
5-5. Indoor Fan Performance
5. Concealed Duct High-Static Pressure Type (D Type)
How to Read the Diagram
The vertical axis is the External Static Pressure (in.WG) while the horizontal axis represents the
Air Flow (CFM). The characteristic curve for the “H,” “Med, ” and “Lo ” fan speed control.
The nameplate values are shown based on the “H ” air flow.
Therefore in the case of 36 Type, the
flow is 1059 CFM , while the External Static Pressure is 0.72 in.WG at “H ” position.
If the external static pressure is too great (due to long extension of duct, for example), the air flow
volume may drop too low at each air outlet.
H
H
M
M
L
883
1059
1236
0.20
0
0.40
0.60
0.80
1.00
H
H,M
M
L
1059
1236
1412
NOTE
Exter
nal Static Pressure
Exter
nal Static Pressure
36 Type
48 Type
(in.WG)
0.20
0
0.40
0.60
0.80
1.00
(in.WG)
Limit line
Limit line
Limit line
Limit line
Air Flow (CFM)
Air Flow (CFM)
H : At shipment