(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the

short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor
units except any one of the outdoor units.

(When shipping: In shorted condition.)

Otherwise the communication of S-net link system is not performed. For a system without link (no con-
nection wiring between outdoor units), do not remove the short plug.

(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 3-1)

3. Electrical Wiring

Outdoor unit

Outdoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

more than 3.3 ft

more than 3.3 ft

Branch
point

16 or fewer

Indoor unit

Indoor unit

Indoor unit

Indoor unit

less than 3.3 ft

Indoor unit

Outdoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

Indoor unit

NO

NO

Branch point

Outdoor unit

Outdoor unit

Outdoor unit

Prohibited

Prohibited

Indoor unit

Indoor unit

Indoor unit

Indoor unit

Indoor unit

CAUTION

(3) Do not install inter-unit control wiring such as star branch

wiring. Star branch wiring causes mis-address setting. (Fig.
3-2)

(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer. (Branches

less than 3.3 ft are not included in the total branch number.) (Fig. 3-3)