Wall-mounted type (k type) – Sanyo CHDZ09053 User Manual
Page 209
4-85
W-3WAY ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
7. Wall-Mounted Type (K Type)
Indoor unit (E)
MODEL No.
KHX2452
Source
208 - 230 V / 1ø / 60 Hz
Controller P.C.B. Ass'y
CR-KR254GXH56A (Microprocessor)
Fan...(Number diameter)
in. (mm)
Cross-flow (1 ... ш3-7/8 (ш100) / 33-3/8 (848))
Fan motor
Model...Nominal output
W
KFT4Q-31A6P-C...30W
Source
208 - 230 V / 1ø / 60 Hz
No. of pole...r.p.m. (230V, High)
rpm
4P... 1,147
Coil resistance
(Ambient temperature 68°F)
Ω
WHT – BRN : 260.7
ORG – YEL : 23.76
WHT – VLT : 42.62
YEL – PNK : 115.9
VLT – ORG : 30.36
Run capacitor
VAC, µF
440 VAC, 1.8 µF
Safety device
fuse
Operating temperature
(17AM033E5-4)
Open °F (°C)
266 ± 14 (130 ± 8)
Close °F (°C)
174 ± 27 (79 ± 15)
Electronic expansion valve
Coil
UKV-U031E
Coil resistance (at 68°F)
Ω
ORG – GRY : 46
YEL – GRY : 46
RED – GRY : 46
BLK – GRY : 46
Valve body
UKV-25D32
Heat exchanger
Coil
Aluminum plate fin / Copper tube
Rows...fin pitch
in. (mm)
2...7 / 128 (1.3)
Face area
ft
2
(m
2
)
2.37 (0.220)