Model selecting and capacity calculator – Sanyo CHDZ09053 User Manual

Page 15

Advertising
background image

2-5

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

1. Model Selecting and Capacity Calculator

Refrigerant Charge Amount at Shipment (for outdoor unit)

CHDZ09053 CHDZ14053

DC

CHDZR09053 CHDZR14053

(oz)

416 416

System Limitations

Max. No. allowable connected outdoor units

2

*1

Max. capacity allowable connected outdoor units

307,200 BTU/h (32 hp, 90 kW)

Max. connectable indoor units

40

Max. allowable indoor/outdoor capacity ratio

50 – 130 %

*1: Up to 2 units can be connected if the system has been extended.

Additional Refrigerant Charge

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4"

(ш6.35)

0.279

ш3/8"

(ш9.52)

0.602

ш1/2"

(ш12.7)

1.38

ш5/8"

(ш15.88)

1.99

ш3/4"

(ш19.05)

2.78

ш7/8"

(ш22.22)

3.93

Required amount of charge = Necessary Amount of Refrigerant

Charge Per Unit + (Amount of refrigerant charge per meter of

each size of liquid tube × its tube length) + (...) + (...)

* Always charge accurately using a scale for weighing.

Table 2-1-1 Necessary Amount of Refrigerant Charge Per Unit

CHDZ09053

CHDZR09053

CHDZ14053

CHDZR14053

113 oz/unit