Installation instructions – Sanyo CHDZ09053 User Manual

Page 42

Advertising
background image

2-32

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

4. Installation Instructions

CAUTION

4-2. Indoor Unit

AVOID:

heat sources, exhaust fans, etc.

damp, humid or uneven locations

indoors (no-ventilation location)

DO:

choose a place as cool as possible.

choose a place that is well ventilated.

select a location where tubing and drain pipe have the

shortest run to the outdoor unit.

allow enough room around the unit for air intake/exhaust

and possible maintenance.

Installation Space

Install the outdoor unit where there is enough space for ven-
tilation. Otherwise the unit may not operate properly. Fig. 4-6
shows the minimum space requirement around the outdoor
units when 3 sides are open and only 1 side is shuttered, with
open space above the unit. The mounting base should be
concrete or a similar material that allows for adequate drain-
age. Make provisions for anchor bolts, platform height, and
other site-specifi c installation requirements.

Leave space open above the

unit.

Construct louvers or other

openings in the wall, if neces-
sary, to ensure adequate venti-
lation.

Do not do any wiring or tubing within 1 ft of the front panel,

because this space is needed as a servicing space for the
compressor.

Ensure a base height of 4 in or more to ensure that drain-

age water does not accumulate and freeze around the
bottom of the unit.

If installing a drain pan, install the drain pan prior to install-

ing the outdoor unit.

*

Make sure there is at least 6 in between the outdoor unit
and the ground.

Also, the direction of the tubing and electrical wiring

should be from the front of the outdoor unit.

NOTE

Out-
door
unit

Heat
source

Hot air

Exhaust fan

Fig. 4-6

More than
2 in.

More than
1.7 ft.

* More than 4 in.

* More than 4 in.

* More than 4 in.

Example of installation of 2 units

(When wall height is below 6 ft.)

* However, be sure to ensure a space of 1 ft. or more at

either the right side or the rear of the unit.

Fig. 4-7

Unit: in.

74

35

35

36-1/4

37-1/2

7-7/8

4

31-1/8

70-1/8

31-1/8

35

Fig. 4-5

Advertising
This manual is related to the following products: