Model selecting and capacity calculator – Sanyo CHDZ09053 User Manual

Page 18

Advertising
background image

2-8

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

Indoor unit

Outdoor unit

Outdoor unit

Indoor unit

Suction tube

Discharge tube

Liquid tube

Balance tube

Room

Hallway

Indoor unit

Room

Indoor unit

Room

Hallway

Indoor unit

Room

Suction tube

Discharge tube

Liquid tube

Gas tube

Liquid tube

4-tube layout

3-tube layout

2-tube layout

Solenoid

valve kit

Solenoid
valve kit

Solenoid
valve kit

1-5. Installation Standards

1. Model Selecting and Capacity Calculator

YES

NO

Relationship between A/C units and refrigerant tubing

Install the solenoid valve kit 98 ft. or less from the indoor unit.
In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat noticeable. It is recom-

mended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside the room.

Common solenoid valve kit

Multiple indoor units under group control can utilize a solenoid valve kit in common.
Categories of connected indoor unit capacities are determined by the solenoid valve kit.

Type of solenoid valve kit

Total capacity of indoor units (BTU/h)

160

19.100 < Total capacity 54.600

56

7.500 Total capacity 19.000

If the capacity range is exceeded, use 2 solenoid valves connected in parallel.

(2) When adding ball valve for outdoor unit

1. Location: Install the ball valve at the main tube of the distribution joint.

2. Installation requirements

• Be sure to install the ball valve up-grade to prevent the inadvertent flow of oil.

• If the ball valve is installed at the outdoor unit (including extension for outdoor unit), face the service port of

the valve toward the outdoor unit side (see above illustration; dotted line) and allow a distance of over 1.6 ft
from the outdoor unit. If the ball valve is installed between the indoor unit (including extension for indoor unit)
and the main tube, face the ball valve toward the indoor unit side (see above illustration; dotted line).

• Use a field supply ball valve.

Main tube

Ball valve (for extension)

To indoor unit

Outdoor unit
for extension

Discharge tube

Balance tube

(Suction tube)

(Planned expansion)

Main tube of distribution joint

Liquid tube

Less than 1.3 ft

Distribution joint

• Install the ball valve at the shortest distance (within 1.3 ft.) from the main tube. If the diameter of the ball valve

is smaller than that of the main tube, use a reducer or the like to reduce the size of the tubing at that location.

NOTE