4-38

W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

3. 1-Way Air Discharge Semi-concealed Type (A Type)

Indoor unit (C)

MODEL No.

AHX1252

Source

208 - 230 V / 1ø / 60 Hz

Controller P.C.B. Ass'y

CR-SXRP56B-B (Microprocessor)

Fan...(Number diameter)

in. (mm)

Centrifugal (1 ... ш 5-1/2 (ш 140))

Fan motor

Model...Nominal output

W

DK8-63E280HB...60W

Source

340 VDC

No. of pole...r.p.m. (230V, High)

rpm

8P...880

Coil resistance

(Ambient temperature 68°F)

Ω

RED – WHT : 53.0

WHT – BLU : 53.0

BLU

– RED : 53.0

Run capacitor

VAC, µF

Safety device

fuse

Operating temperature

Open °F (°C)

285

+4
–5

(141

+2
–3

)

Electronic expansion valve

Coil

UKV-U012E

Coil resistance (at 68°F)

Ω

ORG – GRY : 46

YEL – GRY : 46

RED – GRY : 46

BLK – GRY : 46

Valve body

UKV-18D30

Heat exchanger

Coil

Aluminum plate fin / Copper tube

Rows...fin pitch

in. (mm)

3...7/128 (1.4)

Face area

ft

2

(m

2

)

1.14 (0.106)

Panel

Model No.

PNR-AH1252

Auto louver motor

MP24ZN

Coil resistance (at 77°F)

Ω

380

Ω ± 7% / phase

Drain pump

PLD-12230ST

Rated

V, Hz, W

AC230V, 60Hz, 10.8W

Total head & capacity

in. (mm), gal/

min (cc/min)

24 (610), 0.11 (400)