If the maximum tubing length (L1) exceeds 295 ft (equivalent length), increase the tubing size of the main liquid, gas tubes (LM)
by one rank.
However, the upper limit for the gas tube size is

ø

1-5/8".

Increasing the tubing size of the gas tubes can reduce the loss of capacity caused by longer tubing lengths.
Refer to Table 2-13 to increase the tubing size. However, the maximum allowable tubing length must not be exceeded.

*

The amount of additional refrigerant charge is determined from the liquid tube size only.

Table 2-10 Correction coeffi cient for equivalent length when the size of the gas tube (LM) is increased

Standard tube diameter
(gas tube, in.(mm))

ш1/2"

(ш12.7)

ш5/8"

(ш15.88)

ш3/4"

(ш19.05)

ш7/8"

(ш22.22)

ш1-1/8"

(ш28.58)

Tube diameter after change
(gas tube, in.(mm))

ш5/8"

(ш15.88)

ш3/4"

(ш19.05)

ш7/8"

(ш22.22)

ш1-1/8"

(ш28.58)

ш1-3/8"

(ш34.93)

Equivalent length correction
coefficient

0.4

0.5

0.6

*

When increasing the size of the suction and discharge tubing (LM), multiply by the
correction coeffi cient from Table 2-13 and calculate the equivalent length for section LM.

Tubing equivalent length after size increase
= Standard tubing equivalent length × Equivalent length correction coeffi cient