Meaning of alarm messages – Sanyo CHDZ09053 User Manual

Page 227

Advertising
background image

5-14

Test Run

1

2

3

4

5

6

7

8

7. Meaning of Alarm Messages

Possible cause of malfunction

Thermistor
fault

Protective
device for
compressor is
activated

Indoor thermistor is either open
or damaged.

Outdoor thermistor is either
open or damaged.

Oil sensor fault.

Indoor coil temp. sensor (E1)

Indoor coil temp. sensor (E2)
Indoor coil temp. sensor (E3)

Indoor suction air (room) temp. sensor (TA)

Indoor discharge air temp. sensor (BL)

Comp. No. 1 discharge gas temp. sensor (DISCH1)

Comp. No. 2 discharge gas temp. sensor (DISCH2)

Outdoor No. 1 coil gas temp. sensor (EXG1)

Outdoor No. 1 coil liquid temp. sensor (EXL1)

Outdoor air temp. sensor (AIR TEMP)

Outdoor No. 2 coil gas temp. sensor (EXG2)

Outdoor No. 2 coil liquid temp. sensor (EXL2)

Overload current is detected.
Lock current is detected.

Current is not detected when comp. No. 1 is ON.

Compressor No. 2 current trouble (overcurrent)

Compressor No. 2 current trouble (locked)

Compressor No. 2 CT sensor disconnected or short circuit

Low pressure switch is activated.

EEP ROM on indoor unit P.C.B. failure

Alarm

message

<<F01>>

<<F02>>
<<F03>>

<<F10>>

<<F11>>

F04

F05

F06

F07

F08

F12

F16

F17

F22

F23

F24

F25

F26

F29

F31

H01
H02

H03

H15

H21

H22

H23

H25

H11

H12
H13

H06

H08

H27
H28

(Disconnection, etc.)

High pressure sensor.

EEP ROM on the main or sub outdoor unit PCB has failed.

Compressor No. 2 discharge temp. sensor disconnected

Protective device in indoor unit

Protective device in outdoor
unit is activated.

is activated.

P03

P04

P05

P14

P17

P18

P22

P26

H31

P16

P29

Incorrect discharge temperature. (Comp. No. 1)

Negative (defective) phase.

Incorrect discharge temperature. (Comp. No. 2)

Activation of
protective
device

Outdoor unit fan motor is unusual.

Inverter for compressor is unusual. (DC compressor does not
operate.)

Overcurrent at time of compressor runs more than 80Hz (DCCT
secondary current or ACCT primary current is detected at a time
other than when IPM has tripped.)

Compressor running failure resulting from missing phase in the
compressor wiring, etc. (Start failure not caused by IPM or no gas.)

IPM trip (IPM current or temperature)

Compressor intake port temperature sensor (RDT)

Continued

Negative (defective) N phase.

Protective device for compressor
No. 3 is activated.

Protective device for compressor
No. 2 is activated.

Protective device for compressor
No. 1 is activated.

Low-pressure sensor failure

Compressor 3 discharge temp. sensor failure (DISCH3)

Outdoor No. 3 coil gas temp. sensor (EXG3)

Outdoor No. 3 coil liquid temp. sensor (EXL3)

Compressor No. 3 current trouble (overcurrent)
Compressor No. 3 current trouble (locked)

Compressor No. 3 CT sensor disconnected or short circuit

Compressor No. 3 discharge temp. sensor disconnected

Comp. No. 3 oil sensor

Comp. No. 1 oil sensor
Comp. No. 2 oil sensor

O

2

sensor (detects low oxygen level) activated

Compressor 3 discharge temp. failure

Thermal protector in indoor unit fan motor is activated.
Improper wiring connections of ceiling panel.

Float switch is activated.

<<P01>>

<<P09>>

<<P10>>

High pressure switch or over load relay is activated.
Power supply voltage is unusual. (The voltage is less than 160 V
between L1 and L2 phase.)