Installation instructions – Sanyo CHDZ09053 User Manual

Page 50

Advertising
background image

2-40

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

4. Installation Instructions

4-14. Optional Distribution Joint Kits

See the installation instructions packaged with the distribution joint kit for the installation procedure.

Table 2-11

Model name

Cooling capacity after distribution

Remarks

1. APR-CHRZP900BAB

307.100 BTU/h or less

For outdoor unit

2. APR-RZP224BAB

76.400 BTU/h or less

For indoor unit

3. APR-RZP680BAB

232.000 BTU/h or less

For indoor unit

4. APR-RZP1350BAB

460.700 BTU/h or less

For indoor unit

Tubing size (with thermal insulation)

1. APR-CHRZP900BAB

For outdoor unit (Capacity after distribution joint is 307.100 BTU/h or less.)

11-13/16

11-13/16

13-25/64

D

C

B

E

D

F

3/4

1-1/8

3/8

5/8

1/2

1

Size

7/8

1-1/4

Part B

Part C

Part D

Part E

Part F

Part G

Part H

Part I

Inch

Insulation

Insulation

Joint

Distribution

Insulation

C

C

H

I

H I

E

GF E

E FG

E

F

G

#C

C

E

D

D

E

#C

D

#C

E

F

#C

Suction Tube

Discharge Tube

Liquid Tube

Unit: in.

*Insulators for both the Suction tube and the Discharge tube are the same.
*Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter. So the both
Distribution joints can fit into different tubes. Since the diameter of the tube ends for both Suction and Discharge tube are
different, take care not to connect the distribution joint different. See the " # " marks on the above figures.

Note that the dimension marked with every alphabetical letter in the diagram shows the inner diameter.

Table 2-12 Dimensions for connections of each part