Auto address setting – Sanyo CHDZ09053 User Manual

Page 224

Advertising
background image

5-11

Test Run

1

2

3

4

5

6

7

8

4. Auto Address Setting

Display during automatic address setting

On outdoor main unit PCB

LED

1

2

Blink alternately

*

Do not short-circuit the automatic address setting pin (CN100) again while automatic address setting is in
progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn OFF.

*

When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.

*

LED 1 is D72. LED 2 is D75.

*

If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then perform
automatic address setting again.

Display details of LEDs 1 and 2 on the outdoor unit control PCB

z

z

is blinking

LED 1

LED 2

(

: ON

: Blinking

: OFF)

Display meaning

After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor
units in that system is possible.

After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are
confirmed in that system; however, the number of indoor units does not match the number that was set.

Alternating

Alternating

Automatic address setting is in progress.

Automatic address setting completed.

Simultaneous

At time of automatic address setting, the number of indoor units did not match the number that was set.
“ ” (when indoor units are operating) indication appears on the display.

Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”

Note: “ ” indicates that the solenoid is fused or that there is a CT detection current failure (current is detected when the

compressor is OFF).

Remote controller display