2-33

Design of W-3WAY ECO-i SYSTEM Unit Specifi cations

1

2

3

4

5

6

7

8

4. Installation Instructions

4-3. Shield for Horizontal Exhaust Discharge

It is necessary to install an air-discharge chamber (fi eld sup-
ply) to direct exhaust from the fan horizontally if it is diffi cult
to provide a minimum space of 7 ft between the air-discharge
outlet and a nearby obstacle. (Fig. 4-8)

In regions with heavy snowfall,
the outdoor unit should be
provided with a solid, raised
platform and snow-proof duct-
ing (fi eld supply).(Fig. 4-9)

4-4. Installing the Outdoor Unit in Heavy Snow Ar-

eas

In locations where wind-blown snow can be a problem, snow-
proof ducting (fi eld supply) should be fi tted to the unit and
direct exposure to the wind should be avoided as much as
possible. (Fig. 4-10) The following problems may occur if
proper countermeasures are not taken:

The fan in the outdoor unit may stop running, causing the

unit to be damaged.

There may be no air fl ow.
The tubing may freeze and burst.
The condenser pressure may drop because of strong

wind, and the indoor unit may freeze.

4-5. Precautions When Installing in Heavy Snow

Areas

a) The platform should be higher than the maximum snow

depth. (Fig. 4-9)

b) The 2 anchoring feet of the outdoor unit should be used

for the platform, and the platform should be installed be-
neath the air-intake side of the outdoor unit.

c) The platform foundation must be solid and the unit must

be secured with anchor bolts.

d) When installing on a roof subject to strong wind, counter-

measures must be taken to prevent the unit from being
overturned.

CAUTION

With snow-

(High platform)

Without snow-
proof ducting

proof ducting

(Without platform)

AVOID

Fallen snow

DO

Fig. 4-8

Fig. 4-9

Fig. 4-10