2. Features of W-3WAY ECO-i SYSTEM

2-1. Outline of W-3WAY ECO-i SYSTEM

System

example

ADDITION

CONCENTRATION

CONNECTION

Inverter unit

Inverter unit

If your indoor capacity load changes in the future,
it’s easy to add on both indoor and outdoor units
using the same piping.

*If the additional installment of outdoor and indoor units is
expected, the size of refrigerant piping should be decided
according to the total capacity after the addition.

If indoor/outdoor units need servicing, a ball
valve (optional) cuts off non-operational
units to let other units stay running.

* The capacity after the setting is

made must not exceed 32 PS.

Since all pipings are
concentrated into
one pipe shaft, you
can minimize piping
space and construc-
tion labor

Maximum number of combined outdoor units

Maximum horsepower of combined outdoor units

Maximum mumber of connectable indoor units

Indoor/outdoor unit capacity ratio

Maximum actual tubing length

Maximum level difference (when outdoor unit is lower)

Maximum total tubing length

2

32 HP

40

50~130%

492 ft

164 (131) ft

984 ft

System limitations

Combination of outdoor units
The DC inverter unit can be used independently or in combination.

CAUTION

R407C models and R22 models must not be used in combination with each
other.

1

1

2

10

16

10

16

20

26

32

Total horse

power

Inverter unit

Combination of outdoor units

1

2

1

Solenoid
valve kit

Indoor unit