2. System Design

2-1. System Example

(1) Below are the tables created using the “Sanyo PAC System Diagram Software.” Details of the calculations are shown in (2).

Outdoor

unit 1

Indoor

unit 1

Indoor

unit 2

Indoor

unit 3

Indoor

unit 4

Outdoor

unit 2

Elevation
difference: 33 ft

164 ft

33 ft

33 ft

66 ft

33 ft

33 ft

33 ft

Solenoid valve kit

Selection conditions

Assumes that installation is in a 60 Hz region.

Outdoor unit

Room 1
(indoor unit 1)

Room 2
(indoor unit 2)

Room 3
(indoor unit 3)

Room 4
(indoor unit 4)

Cooling

Air condition (DB/WB)

91.0 / 72.0

78.0 / 64.0

78.0 / 64.0

78.0 / 64.0

78.0 / 64.0

Max. load (BTU/h)

40,000

40,000

30,000

18,000

Heating

Air condition (DB/WB)

37.0 / 35.0

69.0 / 55.0

69.0 / 55.0

69.0 / 55.0

69.0 / 55.0

Max. load (BTU/h)

46,000

46,000

35,000

23,000

Actual tubing length

296 ft

197 ft

230 ft

263 ft

296 ft

Equivalent length (with consideration
for curves, etc.)

365 ft

236 ft

276 ft

316 ft

365 ft

Preliminary selection

Outdoor unit

Room 1
(indoor unit 1)

Room 2
(indoor unit 2)

Room 3
(indoor unit 3)

Room 4
(indoor unit 4)

Selected model

Type

09053+09053

Type 4852

Type 4852

Type 3652

Type 1852

Load (cooling/heating) (BTU/h)

40,000

40,000

30,000

18,000

Rated capacity
(cooling/heating) (BTU/h)

191,000 /

215,000

47,800 /

54,600

47,800 /

54,600

36,000 /

39,000

19,000 /

21,000

(5) Corrected capacity (cooling/

heating) (BTU/h)

159,600 /

156,100

47,400 /

54,600

46,300 /

54,600

34,000 /

38,900

17,500 /

20,600

(7) Actual capacity

(cooling/heating) (BTU/h)

47,400 /

50,900

46,300 /

50,900

34,000 /

36,300

17,500 /

19,200

Total corrected capacity of indoor units (cooling/heating) = 145,200/168,700
Ruc = 145,200/159,600 = 0.910 < 1 Ruh = 168,700/156,100 = 1.081 > 1

Outdoor unit changes

During heating, the corrected outdoor unit capacity is less than the total corrected capacity of all indoor units in the system. As a
result, the actual capacity of each indoor unit is less than the maximum load. Therefore the outdoor unit is increased by one rank.

Outdoor unit

Room 1
(indoor unit 1)

Room 2
(indoor unit 2)

Room 3
(indoor unit 3)

Room 4
(indoor unit 4)

Selected model

Type

14053+09035

Type 4852

Type 4852

Type 3652

Type 1852

Maximum load
(cooling/heating) (BTU/h)

40,000

40,000

30,000

18,000

Rated capacity
(cooling/heating) (BTU/h)

249,100 /

278,100

47,800 /

54,600

47,800 /

54,600

36,000 /

39,000

19,000 /

21,000

(5) Corrected capacity (cooling/

heating) (BTU/h)

208,100 /

201,900

47,400 /

54,600

46,300 /

54,600

34,000 /

38,900

17,500 /

20,600

(7) Actual capacity

(cooling/heating) (BTU/h)

47,400 /

54,600

46,300 /

54,600

34,000 /

38,900

17,500 /

20,600

Total corrected capacity of all indoor units (cooling/heating) = 145,200/163,700
Ruc = 145,200/208,100 = 0.698 < 1 Ruh = 168,700/201,900 = 0.835 < 1