Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 101
 
6F8A0917
- 100 -
Changing the preset output function
The following is an example to show how to change the preset output function from Output state 
hold (1/HOLD) to One-shot pulse output (2:50ms PULSE). 
Switch operation
Display example
Description
I2: PRESET FNC 
 1:HOLD 
Select I2:PRESET FNC from the setting item selection menu. 
The currently set preset count output function (HOLD in this 
example) appears. 
I2: PRESET FNC 
 1:HOLD 
The cursor appears.
I2: PRESET FNC 
 2:50ms PULSE 
Press
to select the setting code 1:50ms PULSE.
I2: PRESET FNC 
 2:50ms PULSE 
The display blinks and the set value is displayed for
confirmation
Press
MENU/ENT
again to write the data. Then the cursor
disappears and the display returns to the condition that the
setting value is displayed.
I2: PRESET FNC
Returns to the menu of setting item selection.