6 preset counter output function – Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual

Page 143

Advertising
background image

6F8A0917

- 142 -

10.6

Preset Counter Output Function

A contact signal is output when the totalized flow count exceeds the preset value (preset count value).

Proceed as follows to use the preset counter output.

Totalizer Setting

• Follows the procedure in 10.2 “Totalizer and Pulse Output” and set necessary

items to the totalizer.

Preset Count Value, Preset
Output Function Setting

• Follow the procedure in 8.2.16 “Preset Counter” and set the preset count value and

output function.

DO/DI Setting

• Follow the procedure in 8.2.14 “Digital I/O Function” and set the digital output

(DO) for use as a preset counter output.
In addition, if you want to reset the totalizer by an external signal, set the DI for
the totalizer counter Reset/Start signal. (Set F3: DI FUNCTN to 2: C RES/STA.)

* Operation for the totalizer control signal can be set using the control signal level

setting described in 8.2.14 “Digital I/O Function.”

When the operation switch in the converter is used to reset the counter, the digital
input function (DI) setting is not needed.