Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 96
 
6F8A0917
- 95 -
Checking the count rate and pulse width
How to check the count rate setting is shown below. 
To check other setting values, select the following function numbers: 
Pulse width mode
H2: PLS MODE
Pulse width
H3: PLS WIDTH
Switch operation
Display example
Description
H1: COUNT RATE 
 1.00000 m3 
Select H1: COUNT RATE from the setting item selection 
menu. 
The currently set count rate appears. 
H1: COUNT RATE
Returns to the menu of setting item selection.
Changing the count rate
The following is an example to change the count rate from 0.01m
3
to 200 l (liter).
Switch operation
Display example
Description
H1: COUNT RATE 
 1.00000 m3 
Select H1: COUNT RATE from the setting item selection 
menu. 
The currently set count rate appears. 
H1: COUNT RATE 
 1.00000 m3 
The cursor appears. 
Press
further to move the cursor to the digit of unit.
H1: COUNT RATE 
 1000.00 l 
 
↓
200.000 l
Change the unit to l. 
Then press
to move the cursor to the desired digit to change
and change the number there. Repeat this operation until 200 l 
appears on the display. 
H1: COUNT RATE 
 200.000 l 
The display blinks and the set value is displayed for
confirmation.
Press
MENU/ENT
again to write the data. Then the cursor
disappears and the display returns to the condition that the set
value is displayed.
H1: COUNT RATE
Returns to the menu of setting item selection.
 
Note: The indicting units for count rate are displayed cyclically as shown below. 
m
3
ml
l
gal
bbl
pt
qt