1 replacing the lf230 converter – Toshiba Tohsiba Electromagnetic Flowmeter Converter L5232 User Manual
Page 31
 
6F8A0917
- 30 -
5.6 Cautionary Notes on Replacing Converter
5.6.1 Replacing the LF230 Converter
The following precautions must be taken to replace the conventional type LF230 with LF232.
Installation
• Since the hole diameter and pitch for mounting fitting, and the dimensions of the LF232 converter
main unit are the same as those of the LF230 converter, it is possible to replace the converter without 
changing the mounting panel, installation space, etc. 
• The operation switches of the LF232 are infrared switches. If direct sunlight hits the display and the
operation section or if there is something nearby that easily reflects light, this kind of light becomes 
disturbance light and the switch operation may not work correctly. Be careful about the installation 
location and angle, or take measures such as providing a sunshade or shield plate so that disturbance 
light does not hit the operation section directly. 
Wiring
• The positions of the LF232 cable ports are the same as those of the LF230. 
• The specifications of the cable ports differ as shown in the table below. 
Table 5.2 Comparison of Cable Port Specifications
LF230
LF232
Ports on the housing
M27 fine pitch thread 
 Depth 0.433 inch (11mm)
G1/2 
Depth 0.433 inch (11mm) 
Material
Stainless steel
Nylon resin
Attached cable 
connection 
specifications 
Waterproof grade
IP67
IP67
Appropriate cable 
diameter 
Excitation and DI/DO cables
 
φ0.433−0.512 inch 
(
φ11−13mm)
Other cables 
 
φ0.394−0.472 inch 
(
φ10−12mm)
φ0.433−0.512 inch 
(
φ11−13mm)
Conduit connection port R (PT) 1/2 male thread
Not provided
Blind plate (seal plate)
Waterproof blind plate 
attached 
Dustproof blind plate attached 
* (Note) 
Note: The blind plate is not a waterproof type. If it is necessary to install the converter where waterproof
structure is needed, take waterproof measures for unused cable ports such as using sealing plugs sold on 
the market. 
 
• Since the terminal block specification of the LF232 is M4 screws, the same as that of the LF230, it is 
possible to connect the cables without changing the cable terminals.